Feeds, phases, breakers, protection, and backup.

Reliable power is the backbone of automatic HVM bollard performance. This page defines utility profiles, UPS/generator tie-ins, and when solar/hybrid makes sense in GCC climates (337 Hot Climate Design). We set voltage/phase standards, demand/diversity rules, and volt-drop limits you’ll prove with 925 Cable Volt-Drop Calculator. Include surge protection and robust earthing (514 Electrical Supply & Protection), then document everything in single-line diagrams for commissioning (631636) and submittals (938 Submission-Pack Guidance). For UAE authority contexts, see SIRA Bollards (UAE). Link back to the parent hubs: this section (510 Power / HPU Topologies) and the chapter hub (500 Automatic HVM Bollard Controls). Link installation pages only if helpful: What to Expect and Installation Guide.

Important: This is a general guide. For live projects we develop a tailored Method Statement & Risk Assessment (MS/RA) and align with authority approvals (e.g., SIRA) where in scope.

511.1 Utility power profiles

Document voltage, phase, short-circuit level, and reliability. Stable supply prevents nuisance trips on automatic HVM bollard panels and protects crash rated bollard lane uptime.

Start by capturing the site’s service voltage (typically 400/230 V), supply diversity assumptions, utility transformer capacity, and voltage drop constraints. Record the available short-circuit level at the main panel—it drives protective device choice and enclosure ratings. Capture brownout/phase imbalance history and planned expansions to avoid undersizing.

For Electrical & Controls reliability, align the utility profile with 518 Power Failure Modes and 542 KPIs & thresholds so uptime targets are realistic.

AspectWhat mattersWhere to verify
PerformanceTested system (bollard + footing)Crash Ratings Explained
OperationsDuty cycles, fail-state, safety devices & measuresInstallation Guide

511.2 Generator/UPS interfaces

Define ATS/STS behavior, runtimes, and backfeed interlocks. Clean interfaces keep HVM bollard sequencing intact during outages (518).

Specify an UPS autonomy to ride through brief outages and a generator start-time budget for longer ones. Document ride-through criteria for the PLC and HPU starters. The control interfaces must avoid mid-stroke transfers—use permissives (bollards up/down/locked) and inhibit logic on generator fail-to-start.

Include backfeed interlocks (mechanical + electrical) and an ATS/STS test mode. Log transfer events via 541 Remote fault logging and surface alarms in 533 SCADA/BMS. Coordinate with 519 Power Test Points for safe proving.

511.3 Solar/hybrid feasibility

Assess irradiance, battery autonomy, and critical loads. Solar can sustain signage and controls while the crash rated bollard drive stays grid/UPS-backed (517).

In GCC climates, panel derating from heat, dust soiling, and shading variability can be significant. Prioritize low-power auxiliaries (beacons, signage, comms) on PV + battery while leaving actuator power on mains/UPS. Cross-check daily/seasonal energy with 517 Energy Budget and ensure nighttime autonomy covers your response window. Where PV is mandated, include a hybrid option with generator fallback and load-shedding tiers.

511.4 Voltages & phases

Standardize 400/230 V or site norm, with clear labeling (347). Consistency reduces errors around HVM bollard panels.

Declare a site-wide standard for supply (e.g., 400/230 V, 50 Hz) and label all enclosures and feeders per 347 Enclosures & Cabling. For electromechanical drives, specify starter type (DOL/soft-starter/VFD) and allowable phase imbalance. For hydraulic units, define heater circuits and control transformers (e.g., 230→24 V) with segregation between power and I/O wiring. Maintain one earthing system choice across the project to simplify protection grading.

511.5 Demand/diversity

Apply realistic concurrency for drives, heaters, and beacons. Right diversity keeps crash rated bollard protection without oversizing (517).

Build an energy/demand model using 517 Energy Budget and actual lane operations. Typical concurrency: one lane moving while adjacent lanes idle; heaters cycling by thermostat; beacons steady. Apply diversity to feeder sizing but preserve worst-case start currents (EFO events) and Ops/hour KPIs. Record assumptions in the assumptions register and validate during 636 Performance & Duty Tests.

511.6 Volt-drop & cable run limits

Set maximum drop and feeder lengths; verify with 925. Limits ensure HVM bollard actuators meet timing.

Define a design drop (e.g., ≤3% feeders, ≤5% total) from main panel to the furthest HPU/panel. Long external runs should use larger CSA, reduced joints, and derating for ambient/sun-load. Verify feeder choices with the 925 Cable Volt-Drop Calculator, and record test points at distribution boards for 519 Power Test Points. Where runs exceed limits, add local sub-panels or relocate HPUs.

511.7 Surge/lighting protection

Specify SPD classes and bonding (514). Protection preserves crash rated bollard electronics in stormy sites.

Use coordinated surge protective devices (Type 1 at service entrance, Type 2 at distribution, Type 3 at sensitive loads) and bond metallic sleeves/frames and ducts to the main earthing bar. Route signal lines with proper separation and add data-line protectors where cables leave buildings. Confirm enclosure IP, cable entries with 516 Enclosure Protection, and log SPD health where monitoring is available (dry contacts to PLC/SCADA).

511.8 Earthing/bonding

Design TN/TT per site; bond sleeves and frames. Proper earths protect HVM bollard safety circuits (343).

Select the project earthing system (TN-S/TN-C-S/TT) with the consultant and utility. Provide low-impedance protective earth to each HPU/enclosure; bond bollard sleeves, gland plates, and any external steelwork. Maintain clean segregation between power PE and signal reference, and test earth fault loop impedance at each panel. Confirm safety circuits in 343 Safety circuits remain within trip times under worst-case supply conditions.

511.9 Evidence & single-line diagrams

Issue SLDs with loads, protections, and interlocks. Evidence speeds crash rated bollard approvals (444, 938).

Produce a project Single-Line Diagram (SLD) set showing sources, feeders, protective devices/ratings, SPDs, earthing, ATS/STS logic, and interlocks with fire alarm/BMS. Cross-reference 632 Power-On & Controls Health, 634 Interlock Matrix Verification, and the 938 Submission-Pack Guidance. Include an index in the 444 Evidence & Documentation style so reviewers can locate revisions quickly.

Related

External resources

511 Supply & Sources — FAQ

How do I size feeders for multiple automatic bollard lanes without oversizing?
Model realistic concurrency: typically one lane moves while others idle, heaters cycle, and beacons remain steady. Apply diversity to steady loads, but preserve worst-case starting currents (including EFO). Verify voltage-drop with the 925 Cable Volt-Drop Calculator and confirm timing during 636 Performance & Duty Tests.
Do I still need a generator if I have a UPS?
A UPS provides short ride-through and clean power; a generator covers extended outages. Use ATS/STS with backfeed interlocks and define transfer logic so bollards don’t switch mid-stroke. Set UPS autonomy to span the generator start window and critical operations.
Is solar practical for powering HVM bollard actuators in GCC climates?
Usually no for actuators: heat derating, dust soiling, and peak current demand make PV impractical. Solar is effective for low-power auxiliaries (signage, beacons, comms) while actuators remain on mains/UPS. Consider hybrid designs with generator fallback and load-shedding tiers.
What SPD types and earthing scheme should I specify?
Use coordinated SPDs: Type 1 at the service, Type 2 at distribution, Type 3 at sensitive loads. Select a site earthing scheme (TN-S/TN-C-S/TT) with the utility/consultant; ensure low-impedance earths at each enclosure and bond sleeves, frames, and ducts to the main earth bar.